Optoelectronics mobile clean room / workshop
Optoelectronics mobile clean room purify cleanliness is generally over 10000, local partial requirements 1000, some require constant temperature and humidity.
Indoor air clean room installation parameters specification required:
Optoelectronics mobile clean room purify cleanliness is generally over 10000, local partial requirements 1000, some require constant temperature and humidity.
Indoor air clean room installation parameters specification required:
Temperature and humidity requirements | temperature is generally 23 + 2 ºC, relative humidity of 55 + 5% |
Large fresh air | to ensure that the amount of fresh air per hour indoor ≥40m3 / h |
Large air | air flow (ventilation frequency is ≥25 times / h) |
Pressure | the main workshop adjacent room ≥5Pa |
Average wind speed | 100: 0.3-0.5m / s |
Noise | ≤65dB (A) |
Illuminance | ≥300LX |
Ventilation times | 100,000 ≥18 times; 10000 ≥30 times; 1000≥50 times |
Floor | use 2mm / 3mm epoxy or PVC flooring, electronic anti-static flooring plant optiona |