Standard Conformity: IEC: 60947-4-1
Insulation Voltage Ui: 750V
Operation Voltage Ue: 690V
Ambient Temperature Range: -5º C + 55º C
Operating Altitude: 3000m
Mounting Position: ± 30° (Vertical Plane)
Contactor CJX2-D RDC6 09 12 18 25 32 40 50 65 80 95
Nominal Current Rating at 415V 50Hz AC3 le A 9 12 18 25 32 40 50 65 80 95
NO. of Poles   3P
NO/NC
3P
NO/NC
3P
NO/NC
3P
NO/NC
3P
NO/NC
3P
1NO+1NC
3P
1NO+1NC
3P
1NO+1NC
3P
1NO+1NC
3P
1NO+1NC
Impulse withstand voltage Uimp KV 6 6 6 6 6 8 8 8 8 8
Making Capacity A 250 250 330 350 560 760 900 950 1100 1120
Breaking Capactiy at 415V A 250 250 330 350 560 760 900 950 1100 1120
AC1 duty: Rated Operational Current le
Max. Power Rating at 415V
A 25 25 32 40 50 60 80 80 125 125
KW 11 11 18 22 25 33 45 45 63 63
AC2/AC3duty: Rated Operational Current le
Max. Power Rating at 415V
Electrical life AC-3 (Refer. Electrical life plot)
A 9 12 18 25 32 40 50 65 80 95
KW/HP 4/5 5.5/7.5 9/12.5 11/15 15/20 22/30 25/35 37/50 45/60 45/60
*10 & sup3; Operations 2000 2000 2000 2000 1500 1500 1500 1500 1500 1500
AC4 Duty: Rated Operational current le
Max. Power Rating at 415V(Refer. Eelectrical life plot)
A 9 12 18 25 32 40 50 65 80 95
KW/HP 4/5 5.5/7.5 9/12.5 11/15 15/20 22/30 25/35 37/50 45/60 45/60
Mechanical life Million Ops. 10 10 10 10 10 8 8 8 8 8
Switching Frequency (No Load) OPS. /Hr. 3600 3600 3600 3600 3600 3000 3000 3000 2000 2000
Impedence Per Pole m. ohm. 2.5 2.5 2.5 2 2 1.5 1.5 1 0.8 0.8
Short Time Current at 40& ordm; C(1sec) A 245 245 320 435 545 735 875 920 1045 1065
Short circuit back Up Fuse Rating A 20 20 32 40 50 63 80 80 100 125
Max. Cable size Sq. mm 4 4 6 10 10 16 25 25 50 50
Tightening Torque Nm 0.8 0.8 0.8 1.2 1.2 3.5 3.5 3.5 4 4
Weight 3P/4P KG 0.34/ 0.34/ 0.35/ 0.5/ 0.52/ 1.08/ 1.08/ 1.08/ 1.3/ 1.3/
Over all Dimension(W*H*D) mm 45*74*82 45*74*82 47*76*87 57*83*95 57*83*100 77*120*116 77*120*116 77*120*116 87*120*127 87*120*127
Operating Voltage Range V 0.7-1.1 0.7-1.1 0.7-1.1 0.7-1.1 0.7-1.1 0.7-1.1 0.7-1.1 0.7-1.1 0.75-1.1 0.75-1.1
Power Consumption (inrush /hold) 50Hz VA 70/8 70/8 110/11 110/11 110/11 200/20 200/20 200/20 200/20 200/20
Power Consumption (inrush /hold) 60Hz VA 80/8 80/8 115/11 115/11 115/11 200/20 200/20 200/20 200/20 200/20
Heat Dissipation 50/60Hz W 1.8-2.7 1.8-2.7 2.5-3.5 3.0-4.0 6.0-10.0 6.0-10.0 6.0-10.0 6.0-10.0 6.0-10.0 6.0-10.0
Coil pick up time
Drop out time
ms 12-22
5-12
12-22
5-12
12-22
5-12
15-24
5-20
15-24
5-20
20-25
8-15
20-25
8-15
20-25
8-15
20-25
8-15
20-25
8-15