IVF(Test tube baby) Laboratory purify cleanliness is generally over 10000, local partial requirements 100-1000, some require constant temperature and humidity.
Indoor air clean room installation parameters specification required:
Temperature and humidity requirements temperature is generally 23 + 2 ºC, relative humidity of 55 + 5%
Large fresh air to ensure that the amount of fresh air per hour indoor ≥40m3 / h
Large air air flow (ventilation frequency is ≥25 times / h)
Pressure the main workshop adjacent room ≥5Pa
Average wind speed 100: 0.3-0.5m / s
Noise 65dB (A)
Illuminance ≥300LX
Ventilation times 100,000 ≥18 times; 10000 ≥30 times; 1000≥50 times
Floor use 2mm / 3mm epoxy or PVC flooring, electronic anti-static flooring plant optiona