Electronic Three Phase Multifunctional Watt Hour Meter Tester

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Beijing

  • Validity to:

    Long-term effective

  • Last update:

    2017-12-08 07:23

  • Browse the number:

    178

Send an inquiries

Company Profile

Beijing GFUVE Electronics Co., Ltd.

By certification [File Integrity]

Contact:Mr. Andy Huang(Mr.)  

Email:

Telephone:

Phone:

Area:Beijing

Address:Beijing

Website: http://guangfuhui.artstx.com/

Product details
GF312 Electronic Three Phase Multifunctional watt hour Meter tester

Roduct Description
It is used to calibrate three phase, single phase, active or reactive energy meter under work, and also it can be used as voltage, current and power meter to measure AC parameter of three phase power line.
Features and Functions
Three phase active or reactive electricity energy meter;
Calibrate three phase, single phase, active or reactive meter error;
Measure U(voltage) of three phase or single phase;
Measure I(current) of three phase or single phase;
Measure active power of three phase or single phase;
Measure reactive power of three phase or single phase;
Measure apparent power of three phase or single phase;
Measure power factor of three phase or single phase;
Measure phase angle between voltage and current;
Measure frequency of power line;
Display vector diagram;
Display waveform of U and I;
Analyze and display content of harmonic of U and I;
Store and display measured data;
Optional 5 A, 20 A, 100 A, 500 A, 1000 A, 2000 A, 3000A current clamp;
Measure CT variable ratio;
Measure the ratio or lag-angle of low-voltage transformer.
Connect to PC, reading record data and real-time measured data by PC, and download calibration parameter.
Test Voltage
Range 5V - 450V
Error ± 0.1% (30V - 450V)
± 0.2% (5V - 30V)
Harmonic 2 nd -- 31 st
Test Current
Range (direct connection) 5mA - 20A
Error (direct connection) ± 0.1% (100mA - 20A)
± 0.2% (10mA - 100mA)
Range (Clamp Current) 5mA - 3000A
Error (Clamp Current) ± 0.2% (100mA - 3000A)
± 0.5% (10mA - 100mA)
Harmonic 2 nd -- 31 st
Power measure error
Active power (direct connection) ± 0.1% (0.1A - 20A)
± 0.2% (0.01A - 0.1A)
Reactive power (direct connection) ± 0.1% (0.1A - 20A)
Energy measure error
Active energy (direct connection) ± 0.1% (0.1A - 20A)
± 0.2% (0.01A - 0.1A)
Reactive energy (direct connection) ± 0.2% (0.1A - 20A)
Phase angle
Range 0º - 360º
Error ± 0.1º
Frequency
Range 45Hz - 65Hz
Pulse output
The current is 0 up to 20A 60000
The current is larger than 20A 600
Pulse ratio 1: 1
Output level 5V
Pulse input
Input channel 1
Input level 5 - 24V
Input frequency Max. 2MHz
Display
Resolution 5" LCD(640× 480)
Function
Vector diagram yes
Waveform yes
Energy accumulation yes
Communication port RS232
Communication with PC yes
Other
Voltage Supply way External power
Voltage Supply 1 220V ± 10%, 50/60Hz ± 2Hz
Voltage Supply 2 Li-polymer battery, size: 110X51X16mm
Nominal output voltage: 7.2V, Capacity: 4000mAh.
Ambient temperature 0-- 40degrees
Relative humidity 15% -- 85%
Instrument Dimensions (W × H × D) (mm) 220× 140× 60
Carry Case Dimensions (W × H × D) (mm) 450× 300× 140
Weight (kg) 1.8kg
Carry Case Weight (kg) 4.2kg