630A 12kv Load Break Disconnecting Switch

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Zhejiang

  • Validity to:

    Long-term effective

  • Last update:

    2017-11-19 20:08

  • Browse the number:

    213

Send an inquiries

Company Profile

QINGCHANG ELECTRIC POWER EQUIPMENT CO., LTD.

By certification [File Integrity]

Contact:Mr. Jolon(Mr.)  

Email:

Telephone:

Phone:

Area:Zhejiang

Address:Zhejiang

Website: http://qcswitchgear.artstx.com/

Product details

SF6-insulated ring main unit and SF6-insulated compact switchgear are used in medium voltage distribution networks. They offer a sealed stainless steel tank which contains all the live components and switching functions. The transformer is protected either by a switch fuse combination or a vacuum circuit breaker.

 

SF6-insulated ring main unit can be supplied as a 2, 3 or 4-way unit in standard configurations with additional equipment according to customer specification.

  

SF6-insulated compact switchgear has a unique flexibility due to its extendibility and the possible combination of fully modular and semi-modular configurations, with a maximum of 5 modules in one SF6-tank.

The units are delivered from the factory ready for installation. Routine tests are carried out on all units/ modules before dispatch. No special tools are required for installing the equipment.

 

 

 

 

ELECTRICAL DATA

 

Gas Insulated Switchgear

C-module

F-module

V-module

Switch

disconnector

Earthing switch

Switch-fuse

combination

Earthing switch

Vacuum

circuit-breaker

Earthing switch

Rated voltage

kV

12/17,5/24

12/17,5/24

12/17,5/24

12/17,5/24

12/17,5/24

12/17,5/24

Power frequency withstand voltage

kV

28/38/50

28/38/50

28/38/50

28/38/50

28/38/50

28/38/50

Impulse withstand voltage

kV

95/95/125

95/95/125

95/95/125

95/95/125

95/95/125

95/95/125

Rated current

A

630/630/630

 

2001)

 

200/200/200

 

Breaking capacities:

 

 

 

 

 

 

 

--active load

A

630/630/630

 

 

 

 

 

--closed loop

A

670/670/670

 

 

 

 

 

--off load cable charging

A

141/141/141

 

 

 

 

 

--off load transformer

A

 

 

20/20/20

 

 

 

--earth fault

A

205/160/160

 

 

 

 

 

--earth fault cable charging

A

117/91/91

 

 

 

 

 

--short-circuit breaking current

kA

 

 

see 2)

 

16/16/16

 

Making capacity

kA

52,5/40/40

52,5/40/40

see 2)

12,5/12,5/12,5

40/40/40

40/40/40

Short time current 0,5 sec 3)

kA

 

 

 

 

16/16/16

 

Short time current 1 sec 4)

kA

 

 

 

5/5/5

16/16/16

 

Short time current 3 sec 5)

kA

21/16/16

21/16/16

 

 

 

16/16/16

Note: 1) Depending on the current rating of the fuse-link  

2) Limited by high voltage fuse-links

3) Maximum rating for bushings Interface A (200 series plug-in)

4) Maximum rating for bushings Interface B (400 series plug-in)

5) Maximum rating for bushings Interface C (400 series bolted)